Sale! View larger

RP-1345 -- Waterside Fouling Performance of Brazed-Plate Type Condensers in Cooling Tower Applications

New product

RP-1345 -- Waterside Fouling Performance of Brazed-Plate Type Condensers in Cooling Tower Applications

Report / Survey by ASHRAE, 2012

Dr. Lorenzo Cremaschi; Dr. Jeffrey D. Spitler; Xiaoxiao Wu; Ellisa Lim; Atharva Barve; Annamalai Ramesh

More details

$12.90

-57%

$30.00

More info

Full Description

Brazed plate heat exchangers (BPHEs) have been recently introduced in the air conditioning industry because they could provide higher heat transfer rate per unit volume and are more compact than conventional tube-and-shell exchangers. This report presents a new experimental methodology and results of waterside thermal performance of brazed-type condensers under fouling operating conditions. High and medium water fouling potentials were developed in laboratory to create conditions that cause severe and medium precipitation and particulate fouling during the experiments. Corrosion and biological fouling were intentionally prevented by chemical inhibitors. Among other advantages, the new methodology is independent from the geographical location of the laboratory and from the local water supply source. Using this technique a Langelier Saturation Index of the water of about 3 - 3.5 was achieved, which represents very severe fouling conditions.

Product Details

Published: 2012 Number of Pages: 214File Size: 1 file , 6.7 MB Product Code(s): D-RP-1345